風扇選用工具
Filter by Criteria
Product Name | Power Supply Voltage [V] |
Size [mm] |
Maximum Air Flow*2 [m3/min] |
Maximum Static Pressure*2 [Pa] |
Variable Speed/ Environmental Resistance |
Alarm and Sensor Output | Fan Product Lines |
---|---|---|---|---|---|---|---|
- *1 Parallel installation is assumed when multiple units are used. Please confirm in advance that it can be installed on your desired control cabinet mounting surface.
- *2 The values of maximum air flow and maximum static pressure may vary depending on the power supply voltage/frequency. For actual values, please refer to the product detail page.
Other Calculation Methods
Here is how to calculate it without using the tool (by calculation, or simply by graph).
Calculation of Required Air Flow
Control Cabinet Material | ||
---|---|---|
Overall Heat Transfer Coefficient | U | [W/(m2 K)] |
Installation Location | ||
Width of the Control Cabinet | W | [m] |
Height of Control Cabinet | H | [m] |
Depth of Control Cabinet | D | [m] |
Surface area of control cabinet | S | [m2] |
Control Cabinet Ambient Temperature | T1 | [℃] |
Internal Permissible Temperature | T2 | [℃] |
Total Heat Generation | Q | [W] |
Desired Safety Factor | Sf |
Required Air Flow | V | [m3/min] |
---|---|---|
V = 1 ÷ 20 × (Q ÷ (T2 − T1) − U × S) × Sf = 1 ÷ 20 × ( ÷ ( − ) − × ) × = |
close
Calculation of Heat Generation
Equipment stored in the panel Please select from the pull-down menu below | Rated Capacity Input Only in Other Cases Please enter |
1 unit
Heat Generation Displays calculation results
|
Number of Units Please enter the number of units | Load Factor | Heat Generation Displays calculation results |
---|
Total Heat Generation (Reference): [W]
技術支援工具
- 馬達選用工具
- 風扇選用工具
- 可委託專門的工作人員協助選用